AWG Wire Gauge Chart

Look up any AWG wire gauge: diameter in mm and inches, cross-sectional area, copper resistance per km, and an approximate current rating, with a to-scale view.

AWG 12 shown to scale (relative to 4/0)

2.053 mm

Diameter

0.0808 in

3.309 mm²

Area

5.21 Ω/km

Resistance

1.59 Ω/1000 ft

41 A

Approx. ampacity

AWGØ mmØ inArea mm²Ω/kmAmps*
4/011.6840.46107.2190.16380
2/09.2660.364867.4310.26283
1/08.2510.324953.4750.32245
26.5440.257633.6310.51181
45.1890.204321.1510.82135
64.1150.16213.3021.3101
83.2640.12858.3662.0673
102.5880.10195.2613.2855
122.0530.08083.3095.2141
141.6280.06412.0818.2832
161.2910.05081.30913.1722
181.0240.04030.82320.9516
200.8120.0320.51833.3111
220.6440.02530.32652.967
240.5110.02010.20584.213.5
260.4050.01590.129133.92.2
280.3210.01260.081212.91.4
300.2550.010.051338.530.86

*Approximate single-conductor chassis-wiring guide — not a code rating.

Why the numbers run backwards

In American Wire Gauge a bigger number means a thinner wire. The scale comes from manufacturing: gauge counts how many times the wire was drawn through successively smaller dies, so more draws = thinner wire.

It is a geometric scale. Each step is a fixed ratio, captured by one formula: d(mm) = 0.127 · 92^((36 − n) / 39). Two handy consequences: every 6 gauges the diameter roughly doubles, and every 3 gauges the cross-sectional area roughly doubles.

Area, resistance and the “/0” sizes

Cross-sectional area is A = π·d² / 4, and resistance follows R = ρ·L / A (copper ρ ≈ 1.72 × 10⁻⁸ Ω·m). Below AWG 1 the sizes are written 1/0, 2/0, 3/0, 4/0 (“one aught” … “four aught”), continuing the scale to ever-thicker conductors.

About the current rating

Ampacity is not a single number — it depends on insulation temperature rating, whether the wire is bundled or in free air, ambient temperature and acceptable voltage drop. The values here are an approximate single-conductor, chassis-wiring guide for orientation. For mains and building wiring, always follow the applicable code (NEC, IEC) and the insulation's rating.

Typical gauges in the wild

  • 22–28 AWG: jumper wires, breadboards, signal and data cables.
  • 18–20 AWG: LED strips, low-power DC, hookup wire.
  • 14–16 AWG: household lighting and general outlets, speaker runs.
  • 10–12 AWG: kitchen/appliance circuits, higher-current DC.
  • 2 AWG – 4/0: service entrances, EV chargers, battery and welding cable.